The protection relay does not accept the
Pickup value
or
Pickup value
Mult
setting if the product of these settings exceeds the
Pickup value
setting range.
The pickup value multiplication is normally done when the inrush detection function
(INR) is connected to the
ENA_MULT
input.
GUID-640654EC-1E77-4ED5-BE41-9EC399B686BA-ANSI V1 EN
Figure 114:
Pickup value behavior with
ENA_MULT
input activated
Phase selection logic
If the fault criteria are fulfilled in the level detector and the directional calculation, the
phase selection logic detects the phase or phases in which the measured current exceeds
the setting. If the phase information matches the
Num of pickup phases
setting, the phase
selection logic activates the timer module.
Timer
Once activated, the timer activates the
PICKUP
output. Depending on the value of the
Operating curve type
setting, the time characteristics are according to DT or IDMT. When
the operation timer has reached the value of
Trip delay time
in the DT mode or the
maximum value defined by the inverse time curve, the
TRIP
output is activated.
Section 4
1MAC059074-MB A
Protection functions
236
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......