Parameter
Values (Range)
Unit
Step
Default
Description
Operating curve type
1=ANSI Ext Inv
2=ANSI Very Inv
3=ANSI Norm Inv
4=ANSI Mod Inv
5=ANSI DT
6=LT Ext Inv
7=LT Very Inv
8=LT Inv
9=IEC Norm Inv
10=IEC Very Inv
11=IEC Inv
12=IEC Ext Inv
13=IEC ST Inv
14=IEC LT Inv
15=IEC DT
17=Programmable
18=RI Type
19=RD Type
15=IEC DT
Selection of time delay curve type
Directional mode
1=Non-directional
2=Forward
3=Reverse
2=Forward
Directional mode
Characteristic angle
-179...180
deg
1
60
Characteristic angle
Max forward angle
0...90
deg
1
80
Maximum phase angle in forward direction
Max reverse angle
0...90
deg
1
80
Maximum phase angle in reverse direction
Min forward angle
0...90
deg
1
80
Minimum phase angle in forward direction
Min reverse angle
0...90
deg
1
80
Minimum phase angle in reverse direction
Table 247:
67/51P Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Type of reset curve
1=Immediate
2=Def time reset
3=Inverse reset
1=Immediate
Selection of reset curve type
Voltage Mem time
0...3000
ms
1
40
Voltage memory time
Pol quantity
1=Self pol
4=Neg. seq. volt.
5=Cross pol
7=Pos. seq. volt.
5=Cross pol
Reference quantity used to determine fault
direction
Section 4
1MAC059074-MB A
Protection functions
252
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......