The voltage slope characteristic is achieved by assigning different values to
Voltage high
limit
and
Voltage low limit
. The effective pickup value calculation is based on the
equations.
Voltage level
Effective pickup value (I> effective)
V <
Voltage low limit
Pickup value low
V ≥
Voltage high limit
Pickup value
If
Voltage low limit
≤ V <
Voltage high limit
,
I
effective
A
A I
C D
C V
>
=
−
− >
−
⋅
−
(
)
(
)
GUID-4236A6A6-504B-4A1B-B91D-263066A187B4 V1 EN
(Equation 6)
A set
Pickup value low
I> set
Pickup value
C set
Voltage high limit
D set
Voltage low limit
Here V represents the measured input voltage. The voltage slope characteristic is
graphically represented.
Voltage
low limit
Pickup value
V
Voltage
high limit
Starting
current
Pickup value low
GUID-E3667B8C-7352-4970-BE53-56EA702DAA47 V1 EN
Figure 129:
Effective pickup value or voltage slope characteristic