Parameter
Values (Range)
Unit
Step
Default
Description
Curve parameter B
0.0000...0.7120
1
0.1217
Parameter B for customer programmable
curve
Curve parameter C
0.02...2.00
1
2.00
Parameter C for customer programmable
curve
Curve parameter D
0.46...30.00
1
29.10
Parameter D for customer programmable
curve
Curve parameter E
0.0...1.0
1
1.0
Parameter E for customer programmable
curve
Table 264:
51V Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Measurement mode
1=RMS
2=DFT
3=Peak-to-Peak
2=DFT
Selects used measurement mode
Control mode
1=Voltage control
2=Input control
3=Voltage and
input Ctl
4=No Volt
dependency
1=Voltage control
Type of control
Minimum trip time
40...60000
ms
1
40
Minimum trip time for IDMT curves
Reset delay time
0...60000
ms
1
20
Reset delay time
4.1.3.8
Monitored data
Table 265:
51V Monitored data
Name
Type
Values (Range)
Unit
Description
PICKUP_DUR
FLOAT32
0.00...100.00
%
Ratio of pickup time / trip time
EFF_ST_VAL_A
FLOAT32
0.00...50.00
xIn
Effective pickup value for
phase A
EFF_ST_VAL_B
FLOAT32
0.00...50.00
xIn
Effective pickup value for
phase B
EFF_ST_VAL_C
FLOAT32
0.00...50.00
xIn
Effective pickup value for
phase C
51V
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
267
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......