Name
Type
Values (Range)
Unit
Description
T_ENA_CLOSE
INT32
0...60000
s
Estimated time to deactivate
BLK_CLOSE
TEMP_AMB
FLOAT32
-99...999
°C
The ambient temperature
used in the calculation
49F
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
4.1.4.9
Technical data
Table 274:
49F Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
current: f
n
±2 Hz
Current measurement: ±1.5% of the set value or
±0.002 × I
n
(at currents in the range of 0.01...4.00 ×
I
n
)
Trip time accuracy
1)
±2.0% of the theoretical value or ±0.50 s
1) Overload current > 1.2 × Trip level temperature
4.1.4.10
Technical revision history
Table 275:
49F Technical revision history
Technical revision
Change
C
Removed the
Sensor available setting parameter
D
Added the
AMB_TEMP
input
E
Internal improvement.
F
Internal improvement.
4.1.5
Three-phase thermal overload protection, two time constants
49T
4.1.5.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Three-phase thermal overload
protection, two time constants
T2PTTR
3Ith>T/G/C
49T
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
275
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......