4.1.8.8
Monitored data
Table 306:
37 Monitored data
Name
Type
Values (Range)
Unit
Description
PICKUP_DUR
FLOAT32
0.00...100.00
%
Ratio of pickup time / trip time
37
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
4.1.8.9
Technical data
Table 307:
37 Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the current
measured: f
n
±2 Hz
±1.5% of the set value or ±0.002 × I
n
Pickup time
Typically <55 ms
Reset time
<40 ms
Reset ratio
Typically 1.04
Retardation time
<35 ms
Trip time accuracy in definite time mode
mode ±1.0% of the set value or ±20 ms
4.1.9
Thermal overload protection for motors 49M
4.1.9.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Thermal overload protection for motors
MPTTR
3Ith>M
49M
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
297
Technical Manual