-VG
IG
RCA
= 0 deg
Max forward angle
Pickup value
Min forward angle
Negative
operation
zone
Positive
operation
zone
GUID-06B18504-D22B-44E5-AB19-3084A1D44C36 V1 EN
Figure 157:
Extended operation area in directional ground-fault protection
4.2.2.6
Measurement modes
The function operates on three alternative measurement modes: "RMS", "DFT" and
"Peak-to-Peak". The measurement mode is selected with the
Measurement mode
setting.
Table 348:
Measurement modes supported by 67/51N, 67/50N stages
Measurement mode
67/51N
67/50N
RMS
x
x
DFT
x
x
Peak-to-Peak
x
x
For a detailed description of the measurement modes, see the
Section 4
1MAC059074-MB A
Protection functions
338
615 series ANSI
Technical Manual