To ensure a sufficient accuracy for the IG and VG measurements, it is required that the
residual voltage exceeds the value set by
Min trip voltage
. If the admittance calculation
mode is "Delta", the minimum change in the residual voltage due to a fault must be 0.01
× Vn to enable the operation. Similarly, the residual current must exceed the value set by
Min trip current
.
The polarity of the polarizing quantity VG can be changed, that is, rotated
by 180 degrees, by setting the
Pol reversal
parameter to "True" or by
switching the polarity of the residual voltage measurement wires.
As an alternative for the internal residual overvoltage-based pickup condition, the neutral
admittance protection can also be externally released by utilizing the
RELEASE
input.
When
Admittance Clc mode
is set to "Delta", the external logic used must be able to give
RELEASE in less than 0.1 s from fault initiation. Otherwise the collected pre-fault values
are overwritten with fault time values. If it is slower,
Admittance Clc mode
must be set to
“Normal”.
Neutral admittance is calculated as the quotient between the residual current and residual
voltage (polarity reversed) fundamental frequency phasors. The
Admittance Clc mode
setting defines the calculation mode.
Admittance Clc mode
= "Normal"
Yo
IG
VG
fault
fault
=
−
GUID-A831002F-5145-4700-8D9A-C80FBF6757AF V1 EN
(Equation 24)
Admittance Clc mode
= "Delta"
Yo
IG
IG
VG
VG
IG
VG
fault
prefault
fault
prefault
=
−
−
−
=
−
(
)
∆
∆
GUID-3AD86A5A-52E7-421E-96CC-C69838CB026C V1 EN
(Equation 25)
Yo
Calculated neutral admittance [Siemens]
IG
fault
Residual current during the fault [Amperes]
VG
fault
Residual voltage during the fault [Volts]
IG
prefault
Prefault residual current [Amperes]
VG
prefault
Prefault residual voltage [Volts]
ΔIG
Change in the residual current due to fault [Amperes]
ΔVG
Change in the residual voltage due to fault [Volts]
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
373
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......