, during an outside fault 21YN measures the following
admittance:
Yo
Y
j
Fdtot
= −
≈ − ⋅
1 15
.
mS
GUID-AD02E209-1740-4930-8E28-AB85637CEF0D V2 EN
(Equation 40)
According to
, during an inside fault 21YN measures the admittance after the
connection of the parallel resistor:
Yo
Y
Y
j B
Bgtot
CC
=
+
≈
+
⋅
(
)
1 73
.
mS
GUID-28AF4976-1872-48A1-ACC7-7CC3B51CD9D8 V2 EN
(Equation 41)
Where the imaginary part of the admittance, B, depends on the tuning of the coil
(compensation degree).
The admittance characteristic is selected to be the combined overconductance and
oversusceptance characteristic ("Box"-characteristics) with four boundary lines:
Operation mode
= "Go, Bo"
Directional mode
= "Non-directional"
The admittance characteristic is set to cover the total admittance of the protected feeder
with a proper margin, see
. Different setting groups can be used to allow
adaptation of protection settings to different feeder and network configurations.
Conductance forward
This setting should be set based on the parallel resistor value of the coil. It must be set to
a lower value than the conductance of the parallel resistor, in order to enable dependable
operation. The selected value should move the boundary line from origin to include some
margin for the admittance operation point due to CT/VT-errors, when fault is located
outside the feeder.
Conductance forward
: 15 A/(15 kV/sqrt(3)) * 0.2 = +0.35 mS corresponding to 3.0 A (at
15 kV). The selected value provides margin considering also the effect of CT/VT-errors
in case of outside faults.
In case of smaller rated value of the parallel resistor, for example, 5 A (at 15 kV), the
recommended security margin should be larger, for example 0.7, so that sufficient margin
for CT/VT-errors can be achieved.
Susceptance forward
By default, this setting should be based on the minimum trip current of 1 A.
Susceptance forward
: 1 A/(15 kV/sqrt(3)) = +0.1 mS
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
397
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......