increased by means of a parallel resistor in a compensation coil. In networks where the
neutral point is grounded through a low resistance, the characteristic angle is always 0º.
As the amplitude of the residual current is independent of the fault location, the selectivity
of the ground-fault protection is achieved with time coordination.
The use of wattmetric protection gives a possibility to use the dedicated inverse definite
minimum time characteristics. This is applicable in large high-impedance grounded
networks with a large capacitive ground-fault current.
In a network employing a low-impedance grounded system, a medium-size neutral point
resistor is used. Such a resistor gives a resistive ground-fault current component of about
200...400 A for an excessive ground fault. In such a system, the directional residual power
protection gives better possibilities for selectivity enabled by the inverse time power
characteristics.
4.2.6.8
Signals
Table 399:
32N Input signals
Name
Type
Default
Description
IG
SIGNAL
0
Residual current
VG
SIGNAL
0
Residual voltage
BLOCK
BOOLEAN
0=False
Block signal for activating the blocking mode
RCA_CTL
BOOLEAN
0=False
Relay characteristic angle control
Table 400:
32N Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip
PICKUP
BOOLEAN
Pickup
4.2.6.9
Settings
Table 401:
32N Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Directional mode
2=Forward
3=Reverse
2=Forward
Directional mode
Current pickup value
0.010...5.000
xIn
0.001
0.010
Minimum trip residual current for deciding fault
direction
Voltage pickup value
0.010...1.000
xUn
0.001
0.010
Pickup value for residual voltage
Power pickup value
0.003...1.000
xPn
0.001
0.003
Pickup value for residual active power
Table continues on next page
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
421
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......