Table 410:
27/59THN Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Voltage selection
1=No voltage
2=Measured VG
3=Calculated V0
4=Phase A
5=Phase B
6=Phase C
2=Measured VG
Type of voltage connection available at
generator terminal
CB open factor
1.00...10.00
0.01
1.00
Multiplication factor for beta when CB is in open
condition
Table 411:
27/59THN Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation Disable / Enable
Table 412:
27/59THN Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Voltage block value
0.010...0.100
xUn
0.001
0.010
Low level blocking for 3rd harmonic differential
protection
Generator CB used
0=No
1=Yes
0=No
Defines if generator circuit breaker exists
Reset delay time
0...60000
ms
1
20
Reset delay time
4.2.7.8
Monitored data
Table 413:
27/59THN Monitored data
Name
Type
Values (Range)
Unit
Description
PICKUP_DUR
FLOAT32
0.00...100.00
%
Ratio of pickup time / trip time
UD_3H
FLOAT32
0.00...40.00
xUn
3rd harmonic differential
voltage amplitude
UB_3H
FLOAT32
0.00...40.00
xUn
3rd harmonic bias voltage
amplitude
U_3H_T
FLOAT32
0.00...40.00
xUn
Terminal side 3rd harmonic
voltage amplitude
U_3H_N
FLOAT32
0.00...40.00
xUn
Neutral side 3rd harmonic
voltage amplitude
Table continues on next page
Section 4
1MAC059074-MB A
Protection functions
436
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......