GFC
release
INTR_EF
PICKUP
TRIP
PEAK_IND
Reset
timer
Trip
timer
Reset
delay
time
Trip
delay
time
IG
VG
GUID-21DD081C-AB4D-4120-A8AB-4F29E2EE4117 V1 EN
Figure 218:
Operation in “Intermittent EF” mode, Peak counter limit = 3
Blocking logic
There are three operation modes in the blocking functionality. The operation modes are
controlled by the
BLOCK
input and the global setting
Configuration/System/Blocking
mode
which selects the blocking mode. The
BLOCK
input can be controlled by a binary
input, a horizontal communication input or an internal signal of the protection relay's
program. The influence of the
BLOCK
signal activation is preselected with the global
setting
Blocking mode
.
The
Blocking mode
setting has three blocking methods. In the "Freeze timers" mode, the
operation timer is frozen to the prevailing value. In the "Block all" mode, the whole
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
455
Technical Manual