Table 419:
67YN Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation Disable / Enable
Operation mode
1=Intermittent EF
3=General EF
4=Alarming EF
3=General EF
Operation criteria
Table 420:
67YN Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
IG/I0 signal Sel
1=Measured IG
2=Calculated I0
1=Measured IG
Measured IG or calculated I0
Vg or V0
1=Measured VG
2=Calculated V0
1=Measured VG
Selection for used Uo signal
Peak counter limit
2...20
1
2
Peak counter limit for restriking EF
Pickup delay time
30...60000
ms
1
30
Pickup delay time
Reset delay time
0...60000
ms
1
500
Reset delay time
Pol reversal
0=False
1=True
0=False
Rotate polarizing quantity
4.2.8.8
Monitored data
Table 421:
67YN Monitored data
Name
Type
Values (Range)
Unit
Description
PICKUP_DUR
FLOAT32
0.00...100.00
%
Ratio of pickup time / trip time
FAULT_DIR
Enum
0=unknown
1=forward
2=backward
3=both
Detected fault direction
DIRECTION
Enum
0=unknown
1=forward
2=backward
3=both
Direction information
ANGLE
FLOAT32
-180.00...180.00
deg
Angle between operating
angle and characteristic angle
67YN
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
459
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......