Commissioning
The correct settings, which are
CT connection type
,
Winding 1 type
,
Winding 2 type
and
Clock number
, for the connection group compensation can be verified by monitoring the
angle values
I_ANGL_A1_B1
,
I_ANGL_B1_C1
,
I_ANGL_C1_A1
,
I_ANGL_A2_B2
,
I_ANGL_B2_C2
,
I_ANGL_C2_A2
,
I_ANGL_A1_A2
,
I_ANGL_B1_B2
and
I_ANGL_C1_C2
while injecting the current into the transformer.
These angle values are calculated from the compensated currents. See signal description
from Monitored data table.
When a station service transformer is available, it can be used to provide current to the
high voltage side windings while the low voltage side windings are short-circuited. This
way the current can flow in both the high voltage and low voltage windings. The
commissioning signals can be provided by other means as well. The minimum current to
allow for phase current and angle monitoring is 0.015 I
r
.
GUID-5ACBF127-85A3-4E5E-A130-9F7206A2DB4C V1 EN
Figure 261:
Low voltage test arrangement. The three-phase low voltage source can
be the station service transformer.
The
Tapped winding
control setting parameter has to be set to “Not in use” to make sure
that the monitored current values are not scaled by the automatic adaptation to the tap
changer position. When only the angle values are required, the setting of
Tapped winding
is not needed since angle values are not affected by the tap changer position adaptation.
When injecting the currents in the high voltage winding, the angle values
I_ANGL_A1_B1
,
I_ANGL_B1_C1
,
I_ANGL_C1_A1
,
I_ANGL_A2_B2
,
I_ANGL_B2_C2
and
I_ANGL_C2_A2
have to show +120 deg. Otherwise the phase
order can be wrong or the polarity of a current transformer differs from the polarities of the
other current transformers on the same side.
If the angle values
I_ANGL_A1_B1
,
I_ANGL_B1_C1
and
I_ANGL_C1_A1
show
-120 deg, the phase order is wrong on the high voltage side. If the angle values
I_ANGL_A2_B2
,
I_ANGL_B2_C2
and
I_ANGL_C2_A2
show -120 deg, the phase
order is wrong on the low voltage side. If the angle values
I_ANGL_A1_B1
,
Section 4
1MAC059074-MB A
Protection functions
526
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......