Name
Type
Default
Description
I_C(2)
SIGNAL
0
Phase C secondary current
BLOCK
BOOLEAN
0=False
Block
BLK_OPR_LS
BOOLEAN
0=False
Blocks trip outputs from biased stage
BLK_OPR_HS
BOOLEAN
0=False
Blocks trip outputs from instantaneous stage
Table 434:
87T Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip combined
OPR_LS
BOOLEAN
Trip from low set
OPR_HS
BOOLEAN
Trip from high set
BLKD2H
BOOLEAN
2nd harmonic restraint block status
BLKD5H
BOOLEAN
5th harmonic restraint block status
BLKDWAV
BOOLEAN
Waveform blocking status
4.3.2.8
Settings
Table 435:
87T Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
High trip value
500...3000
%Ir
10
1000
Instantaneous stage setting
Low trip value
5...50
%Ir
1
20
Basic setting for biased operation
Slope section 2
10...50
%
1
30
Slope of the second line of the operating
characteristics
End section 2
100...500
%Ir
1
150
Turn-point between the second and the third
line of the operating characteristics
Restraint Mode
5=Waveform
6=2.h + waveform
8=5.h + waveform
9=2.h + 5.h + wav
9=2.h + 5.h + wav
Restraint Mode
Pickup value 2.H
7...20
%
1
15
The ratio of the 2. harmonic to fundamental
component required for blocking
Pickup value 5.H
10...50
%
1
35
The ratio of the 5. harmonic to fundamental
component required for blocking
Section 4
1MAC059074-MB A
Protection functions
532
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......