in terms of cost and production loss are often serious, which makes the differential
protection an important protection function.
The stability of the differential protection is enhanced by a DC restraint feature. This
feature decreases the sensitivity of the differential protection optionally for a temporary
time period to avoid an unnecessary disconnection of the motor during the external faults
that have a fault current with high DC currents. 87G, 87M also includes a CT saturation-
based blocking which prevents unnecessary tripping in case of the detection of the
magnetizing inrush currents which can be present at the switching operations,
overvoltages or external faults.
4.3.5.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The corresponding
parameter values are “Enable” and “Disable”.
The operation of 87G, 87M can be described using a module diagram. All the modules in
the diagram are explained in the next sections.
GUID-206742C6-5514-41BE-A4F3-2FE0DA9946D5-ANSI V1 EN
Figure 288:
Functional module diagram
Differential and bias calculation
Differential calculation module calculates the differential current. The differential current
is the difference in current between the phase and neutral sides of the machine. The phase
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
569
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......