Table 481:
46 Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Type of reset curve
1=Immediate
2=Def time reset
3=Inverse reset
1=Immediate
Selection of reset curve type
Table 482:
46 Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation Disable / Enable
Curve parameter A
0.0086...120.0000
1
28.2000
Parameter A for customer programmable
curve
Curve parameter B
0.0000...0.7120
1
0.1217
Parameter B for customer programmable
curve
Curve parameter C
0.02...2.00
1
2.00
Parameter C for customer programmable
curve
Curve parameter D
0.46...30.00
1
29.10
Parameter D for customer programmable
curve
Curve parameter E
0.0...1.0
1
1.0
Parameter E for customer programmable
curve
Table 483:
46 Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Minimum trip time
20...60000
ms
1
20
Minimum trip time for IDMT curves
Reset delay time
0...60000
ms
1
20
Reset delay time
4.4.1.8
Monitored data
Table 484:
46 Monitored data
Name
Type
Values (Range)
Unit
Description
PICKUP_DUR
FLOAT32
0.00...100.00
%
Ratio of pickup time / trip time
46
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
Section 4
1MAC059074-MB A
Protection functions
592
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......