Figure 312:
Behavior of different IDMT reset modes. Operate signal is based on
settings Type of reset curve = “Def time reset” and Type of time reset=
“Freeze Op timer”. The effect of other reset modes is also presented
The
Time multiplier
setting is used for scaling the IDMT trip times.
The
Minimum trip time
setting parameter defines the minimum desired trip time for
IDMT. The setting is applicable only when the IDMT curves are used.
The
Minimum trip time
setting should be used with care because the
operation time is according to the IDMT curve, but always at least the
value of the
Minimum trip time
setting. For more information, see the
IDMT curves for overcurrent protection
Section 4
1MAC059074-MB A
Protection functions
622
615 series ANSI
Technical Manual