rest of the network. There is then a risk of an autoreclosure taking place when the voltages
of different parts of the network do not synchronize, which is a straining incident for the
power station. Another risk is that the generator can lose synchronism during the network
fault. A sufficiently fast trip of the utility circuit breaker of the power station can avoid
these risks.
The lower the three-phase symmetrical voltage of the network is, the higher is the
probability that the generator loses the synchronism. The positive-sequence voltage is
also available during asymmetrical faults. It is a more appropriate criterion for detecting
the risk of loss of synchronism than, for example, the lowest phase-to-phase voltage.
Analyzing the loss of synchronism of a generator is rather complicated and requires a
model of the generator with its prime mover and controllers. The generator can be able to
trip synchronously even if the voltage drops by a few tens of percent for some hundreds
of milliseconds. The setting of 47U, 27PS is thus determined by the need to protect the
power station from the risks of the islanding conditions since that requires a higher setting
value.
The loss of synchronism of a generator means that the generator is unable to operate as a
generator with the network frequency but enters into an unstable condition in which it
operates by turns as a generator and a motor. Such a condition stresses the generator
thermally and mechanically. This kind of loss of synchronism should not be mixed with
the one between an island and the utility network. In the islanding situation, the condition
of the generator itself is normal but the phase angle and the frequency of the phase-to-
phase voltage can be different from the corresponding voltage in the rest of the network.
The island can have a frequency of its own relatively fast when fed by a small power
station with a low inertia.
47U, 27PS complements other loss-of-grid protection principles based on the frequency
and voltage operation.
Motor stalling and failure to start can lead to a continuous undervoltage. The positive-
sequence undervoltage is used as a backup protection against the motor stall condition.
4.5.5.6
Signals
Table 547:
47U,27PS Input signals
Name
Type
Default
Description
V
1
SIGNAL
0
Positive phase sequence voltage
BLOCK
BOOLEAN
0=False
Block signal for activating the blocking mode
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
639
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......