4.5.7.8
Monitored data
Table 570:
27RT Monitored data
Name
Type
Values (Range)
Unit
Description
27RT
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
4.5.7.9
Technical data
Table 571:
27RT Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
voltage:
f
n
±2 Hz
±1.5% of the set value or ±0.002 × V
n
Pickup time
1)2)
Typically 40 ms
Reset time
Based on maximum value of
Recovery time setting
Trip time accuracy
±1.0% of the set value or ±20 ms
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
1) Tested for
Num of pickup phases = 1 out of 3, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
4.5.8
Voltage vector shift protection 78V
4.5.8.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Voltage vector shift protection
VVSPPAM
VS
78V
4.5.8.2
Function block
V_A_AB
V_B_BC
V_C_CA
BLOCK
TRIP
78V
INT_BLKD
GUID-87689571-BB05-4911-B2A9-23CCC8EA665C V1 EN
Figure 333:
Function block
Section 4
1MAC059074-MB A
Protection functions
666
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......