Impedance calculation
This module calculates the positive-sequence impedance (Z1) using positive-sequence
voltage and current. For the module to calculate impedance it is required that the positive-
sequence current is above
Min Ps Seq current
setting and the negative-sequence current
is below the
Max Ng Seq current
setting.
The calculated positive-sequence impedance amplitude Z1_AMPL and angle
Z1_ANGLE are available in ohms and degrees, respectively, in the Monitored data view.
The calculated impedance is converted to ohms as the operating
characteristics are defined with the ohm settings.
Out of step detection
The operating characteristic is a circular offset mho on the impedance plane with two pair
of blinders. The mho characteristic is defined with the
Forward reach
,
Reverse reach
, and
Impedance angle
settings.
Forward reach
defines the impedance from the origin to the
edge of circle on the top side.
Reverse reach
defines the impedance from the origin to the
edge of the circle on the bottom side. The diameter of the mho characteristics is the sum of
Forward reach
and
Reverse reach
settings. Two sets of blinders are defined by
Inner
blinder R
and
Outer blinder R
intercepting at R-axis. The blinders are at the same angle as
the
Impedance angle
. The second blinder of each outer and inner pair is automatically
made symmetrical with the origin of the R-X plane.
For a correct operation, it is required that the setting for
Inner blinder R
is
less than the setting for
Outer blinder R
.
The circular mho characteristic can be further divided into two zones by setting
Zone 2
enable
to “Yes”. The boundary between zones is set using the setting
Zone 1 reach
. The
lower portion of the circle, Zone 1, is separated from the upper portion, Zone 2, by a line,
perpendicular to the blinders, located at a set percentage of the
Forward reach
setting
from the origin.
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
687
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......