drop out-of-step. The reason is the steady-state stability limit as defined by the load angle
being 90°, which can only be reached when the unit is underexcited.
Q (Reactive power) p.u.
P (Active power) p.u.
A
B
C
D
F
E
0.0
0.8
0.6
0.5
0.3
1.0
0.9
Generator
Motor
Over-Excitation
Under-Excitation
H
X
e
=0.2
X
s
=0.0
37
o
18
o
Where,
AB= Field current limit
BC= Stator current limit
CD= End region heating limit of stator. Due to leakage flux
BH= Possible active power limit due to turbine output power limitation
EF= Steady -state limit without AVR
GUID-FD5EDD69-0D03-4A97-A1AB-46C755F531A5 V2 EN
Figure 348:
Capability curve of a synchronous generator
40 protects the synchronous machines against an unstable operation due to loss of
excitation. A partial or total loss of excitation causes a reactive power intake from the
network to the machine, and the reactance of the system viewed from the machine
terminals turns negative. This kind of drop-of-reactance condition can be detected by
measuring the impedance of the system.
The operating characteristic is an offset-mho circle in the impedance plane, and the circle
is parameterized with the
Offset
,
Diameter
and
Displacement
setting values.
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
701
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......