GUID-200BC4CB-8B33-4616-B014-AFCC99ED9224 V2 EN
Figure 379:
Time delay for cumulative start
This module also protects the motor from consecutive start-ups. When the
LOCK_START
output is active,
T_RST_ENA
shows the possible time for next restart. The value of
T_RST_ENA
is calculated by the difference of
Restart inhibit time
and the elapsed time
from the instant
LOCK_START
is enabled.
When the
ST_EMERG_ENA
emergency start is set high, the value of the cumulative start-
up time counter is set to
Cumulative time Lim
- 60s ·
Emg start Red rate
. This disables
LOCK_START
and in turn makes the restart of the motor possible.
This module also calculates the total number of start-ups occurred,
START_CNT
. The
value can be reset from the Clear menu.
The old
Number of motor start-ups occurred
counter value (
START_CNT
) can be taken
into use by writing the value to the
Ini start up counter
parameter and resetting the value
via the Clear menu from WHMI or LHMI.
The calculated values of
T_RST_ENA
,
T_ST_CNT
and
START_CNT
are available in the
Monitored data view.
The activation of the
BLK_LK_ST
input signal deactivates the
LOCK_START
output.
The activation of the
BLOCK
input signal resets the cumulative start-up counter module.
4.10.5
Application
When a motor is started, it draws a current well in excess of the motor's full-load rating
throughout the period it takes for the motor to run up to the rated speed. The motor starting
Section 4
1MAC059074-MB A
Protection functions
756
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......