4.10.9
Technical data
Table 658:
66/51LRS Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
current: f
n
±2 Hz
±1.5% of the set value or ±0.002 × I
n
Pickup time
1)2)
Minimum
Typical
Maximum
I
Fault
= 1.1 × set
Pickup
detection A
27 ms
30 ms
34 ms
Trip time accuracy
±1.0% of the set value or ±20 ms
Reset ratio
Typically 0.90
1) Current before = 0.0 × I
n
, f
n
= 50 Hz, overcurrent in one phase, results based on statistical distribution of
1000 measurements
2) Includes the delay of the signal output contact
4.10.10
Technical revision history
Table 659:
STTPMSU Technical revision history66/51LRS Technical revision history
Technical revision
Change
B
Internal improvement
C
Added setting
Ini start up counter.
4.11
Multipurpose protection MAP
4.11.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Multipurpose protection
MAPGAPC
MAP
MAP
4.11.2
Function block
MAP
AI_VALUE
TRIP
PICKUP
BLOCK
ENA_ADD
GUID-D9D5B5B3-27B1-42ED-A429-A887E8D2A376 V1 EN
Figure 382:
Function block
Section 4
1MAC059074-MB A
Protection functions
762
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......