occurs within the trip time up counting, the reset timer is activated. If the drop-off time
exceeds
Reset delay time
, the operation timer is reset.
The
BLOCK
input can be controlled with a binary input, a horizontal communication input
or an internal signal of the relay program. The activation of the
BLOCK
input prevents the
BLK2H
output from being activated.
It is recommended to use the second harmonic and the waveform based
inrush blocking from the 87T function, if available.
5.1.5
Application
Transformer protections require high stability to avoid tripping during magnetizing inrush
conditions. A typical example of an inrush detector application is doubling the pickup
value of an overcurrent protection during inrush detection.
The inrush detection function can be used to selectively block overcurrent and ground-
fault function stages when the ratio of second harmonic component over the fundamental
component exceeds the set value.
Other applications of this function include the detection of inrush in lines connected to a
transformer.
1MAC059074-MB A
Section 5
Protection related functions
615 series ANSI
769
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......