5.1.9
Technical data
Table 675:
INR Technical data
Characteristic
Value
Operation accuracy
At the frequency f = f
n
Current measurement:
±1.5% of the set value or ±0.002 × I
n
Ratio I2f/I1f measurement:
±5.0% of the set value
Reset time
+35 ms / -0 ms
Reset ratio
Typically 0.96
Trip time accuracy
+35 ms / -0 ms
5.1.10
Technical revision history
Table 676:
INR Technical revision history
Technical revision
Change
B
Internal improvement
C
Internal improvement
5.2
Circuit breaker failure protection 50BF
5.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Circuit breaker failure protection
CCBRBRF
3I>/Io>BF
50BF
5.2.2
Function block
GUID-12D6BD6F-2B26-453D-B62F-FC134EC98931 V3 EN
Figure 387:
Function block
Section 5
1MAC059074-MB A
Protection related functions
772
615 series ANSI
Technical Manual