5.3
Master trip 86/94
5.3.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Master trip
TRPPTRC
Master Trip
86/94
5.3.2
Function block
A071286-ANSI V2 EN
Figure 394:
Function block
5.3.3
Functionality
The master trip function 86/94 is intended to be used as a trip command collector and
handler after the protection functions. The features of this function influence the trip
signal behavior of the circuit breaker. The minimum trip pulse length can be set when the
non-latched mode is selected. It is also possible to select the latched or lockout mode for
the trip signal.
5.3.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The corresponding
parameter values are “Enable” and “Disable”.
When the 86/94 function is disabled, all trip outputs which are intended to
go through the function to the circuit breaker trip coil are blocked.
The operation of 86/94 can be described with a module diagram. All the modules in the
diagram are explained in the next sections.
Section 5
1MAC059074-MB A
Protection related functions
784
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......