5.3.5
Application
All trip signals from different protection functions are routed through the trip logic. The
most simplified application of the logic function is linking the trip signal and ensuring that
the signal is long enough.
The tripping logic in the protection relay is intended to be used in the three-phase tripping
for all fault types (3ph operating). To prevent the closing of a circuit breaker after a trip,
86/94 can block the 52 closing.
86/94 is intended to be connected to one trip coil of the corresponding circuit breaker. If
tripping is needed for another trip coil or another circuit breaker which needs, for example,
different trip pulse time, another trip logic function can be used. The two instances of the
PTRC function are identical, only the names of the functions, 86/94-1 and 86/94-2, are
different. Therefore, all references made to only 86/94-1 apply to 86/94-2 as well.
The inputs from the protection functions are connected to the
TRIP
input. Usually, a logic
block OR is required to combine the different function outputs to this input. The
TRIP
output is connected to the binary outputs on the IO board. This signal can also be used for
other purposes within the protection relay, for example when starting the breaker failure
protection.
86/94 is used for simple three-phase tripping applications.
Section 5
1MAC059074-MB A
Protection related functions
786
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......