6.5.8
Monitored data
Table 773:
60 Monitored data
Name
Type
Values (Range)
Unit
Description
60
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
6.5.9
Technical data
Table 774:
60 Technical data
Characteristic
Value
Trip time
1)
NPS function
V
Fault
= 1.1 × set
Neg
Seq voltage Lev
<33 ms
V
Fault
= 5.0 × set
Neg
Seq voltage Lev
<18 ms
Delta function
ΔV = 1.1 × set
Voltage
change rate
<30 ms
ΔV = 2.0 × set
Voltage
change rate
<24 ms
1) Includes the delay of the signal output contact, f
n
= 50 Hz, fault voltage with nominal frequency injected from
random phase angle, results based on statistical distribution of 1000 measurements
6.5.10
Technical revision history
Table 775:
60 Technical revision history
Technical revision
Change
B
Internal improvement
C
Internal improvement
D
Function name changed from SEQRFUF to
SEQSPVC