A071105 V2 EN
Figure 455:
Functional module diagram for calculating inactive days and alarm for
circuit breaker operation monitoring
Inactivity timer
The module calculates the number of days the circuit breaker has remained inactive, that
is, has stayed in the same open or closed state. The calculation is done by monitoring the
states of the
POSOPEN
and
POSCLOSE
auxiliary contacts.
The inactive days
INA_DAYS
is available in the monitored data view. It is also possible
to set the initial inactive days with the
Ini inactive days
parameter.
Alarm limit check
When the inactive days exceed the limit value defined with the
Inactive Alm days
setting,
the
MON_ALM
alarm is initiated. The time in hours at which this alarm is activated can be
set with the
Inactive Alm hours
parameter as coordinates of UTC. The alarm signal
MON_ALM
can be blocked by activating the binary input
BLOCK
.
7.1.4.3
Breaker contact travel time
The Breaker contact travel time module calculates the breaker contact travel time for the
closing and opening operation. The operation of the breaker contact travel time
measurement can be described with a module diagram. All the modules in the diagram are
explained in the next sections.
A071106 V4 EN
Figure 456:
Functional module diagram for breaker contact travel time
Traveling time calculator
The travel time can be calculated using two different methods based on the setting
Travel
time Clc mode
.
Section 7
1MAC059074-MB A
Condition monitoring functions
882
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......