7.1.9
Technical data
Table 788:
52CM Technical data
Characteristic
Value
Current measuring accuracy
±1.5% or ±0.002 × I
n
(at currents in the range of 0.1…10 × I
n
)
±5.0%
(at currents in the range of 10…40 × I
n
)
Operate time accuracy
±1.0% of the set value or ±20 ms
Travelling time measurement
+10 ms / -0 ms
7.1.10
Technical revision history
Table 789:
52CM Technical revision history
Technical revision
Change
B
Added the possibility to reset spring charge time and
breaker travel times
C
Removed the DIFTRVTOPALM and
DIFTRVTCLALM outputs and the corresponding
Open Dif alarm time and Close Dif alarm time setting
parameters
D
The
Operation cycle setting parameter renamed to
Initial CB Rmn life. The IPOW_A (_B, _C) range
changed.
E
Maximum value of initial circuit breaker remaining life
time setting (
Initial CB Rmn life) changed from 9999
to 99999. Added support for measuring circuit
breaker travelling time from opening/closing
command and auxiliary contact state signal change.
F
Alarm Op number range increased from 9999 to
99999.
Lockout Op number setting range increased
from 9999 to 99999.
Counter initial value setting
range increased from 9999 to 99999.
Section 7
1MAC059074-MB A
Condition monitoring functions
896
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......