8.1.6.2
Function block
A070778-ANSI V1 EN
Figure 471:
Function block
8.1.6.3
Signals
Table 808:
IG Input signals
Name
Type
Default
Description
IG
SIGNAL
0
Ground current
BLOCK
BOOLEAN
0=False
Block signal for all binary outputs
Table 809:
IG Output signals
Name
Type
Description
HIGH_ALARM
BOOLEAN
High alarm
HIGH_WARN
BOOLEAN
High warning
8.1.6.4
Settings
Table 810:
IG Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation Disable / Enable
A Hi high limit res
0.00...40.00
xIn
1
0.20
High alarm current limit
A high limit res
0.00...40.00
xIn
1
0.05
High warning current limit
A deadband res
100...100000
1
2500
Deadband configuration value for integral
calculation. (percentage of difference between
min and max as 0,001 % s)
Table 811:
IG Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Measurement mode
1=RMS
2=DFT
2=DFT
Selects used measurement mode
Section 8
1MAC059074-MB A
Measurement functions
914
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......