8.1.11.6
Technical data
Table 841:
P, E Technical data
Characteristic
Value
Operation accuracy
At all three currents in range 0.10…1.20 × I
n
At all three voltages in range 0.50…1.15 × V
n
At the frequency f
n
±1 Hz
±1.5% for apparent power S
±1.5% for active power P and active energy
1)
±1.5% for reactive power Q and reactive energy
2)
±0.015 for power factor
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
1) |PF| >0.5 which equals |cosφ| >0.5
2) |PF| <0.86 which equals |sinφ| >0.5
8.1.11.7
Technical revision history
Table 842:
P, E Technical revision history
Technical revision
Change
B
Demand values added to Monitored data. Recorded
data added to store minimum and maximum demand
values with timestamps.
C
Internal improvement.
D
Internal improvement.
8.1.12
Single-phase power and energy measurement SP, SE
8.1.12.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Single-phase power and energy
measurement
SPEMMXU
SP, SE
SP, SE
Section 8
1MAC059074-MB A
Measurement functions
930
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......