For example, six setting groups can be controlled with three binary inputs. The
SG
operation mode
is set to “Logic mode 2” and inputs
BI_SG_2
and
BI_SG_5
are
connected together the same way as inputs
BI_SG_3
and
BI_SG_6
.
Table 35:
SG operation mode = “Logic mode 1”
Input
BI_SG_2
BI_SG_3
BI_SG_4
BI_SG_5
BI_SG_6
Active group
FALSE
FALSE
FALSE
FALSE
FALSE
1
TRUE
FALSE
FALSE
FALSE
FALSE
2
any
TRUE
FALSE
FALSE
FALSE
3
any
any
TRUE
FALSE
FALSE
4
any
any
any
TRUE
FALSE
5
any
any
any
any
TRUE
6
Table 36:
SG operation mode = “Logic mode 2”
Input
BI_SG_2
BI_SG_3
BI_SG_4
BI_SG_5
BI_SG_6
Active group
FALSE
FALSE
FALSE
any
any
1
TRUE
FALSE
FALSE
any
any
2
any
TRUE
FALSE
any
any
3
any
any
TRUE
FALSE
FALSE
4
any
any
TRUE
TRUE
FALSE
5
any
any
TRUE
any
TRUE
6
The setting group 1 can be copied to any other or all groups from HMI (Copy group 1).
Section 3
1MAC059074-MB A
Basic functions
88
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......