analog channel. In addition, the user can enable or disable each analog channel of the
disturbance recorder by setting the
Operation
parameter of the corresponding analog
channel to “Enable” or “Disable”.
All analog channels of the disturbance recorder that are enabled and have a valid signal
type mapped are included in the recording.
8.2.2.2
Triggering alternatives
The recording can be triggered by any or several of the following alternatives:
•
Triggering according to the state change of any or several of the binary channels of
the disturbance recorder. The user can set the level sensitivity with the
Level trigger
mode
parameter of the corresponding binary channel.
•
Triggering on limit violations of the analog channels of the disturbance recorder (high
and low limit)
•
Manual triggering via the
Trig recording
parameter (LHMI or communication)
•
Periodic triggering.
Regardless of the triggering type, each recording generates the Recording started and
Recording made events. The Recording made event indicates that the recording has been
stored to the non-volatile memory. In addition, every analog channel and binary channel
of the disturbance recorder has its own
Channel triggered
parameter. Manual trigger has
the
Manual triggering
parameter and periodic trigger has the
Periodic triggering
parameter.
Triggering by binary channels
Input signals for the binary channels of the disturbance recorder can be formed from any
of the digital signals that can be dynamically mapped. A change in the status of a
monitored signal triggers the recorder according to the configuration and settings.
Triggering on the rising edge of a digital input signal means that the recording sequence
starts when the input signal is activated. Correspondingly, triggering on the falling edge
means that the recording sequence starts when the active input signal resets. It is also
possible to trigger from both edges. In addition, if preferred, the monitored signal can be
non-triggering. The trigger setting can be set individually for each binary channel of the
disturbance recorder with the
Level trigger mode
parameter of the corresponding binary
channel.
Triggering by analog channels
The trigger level can be set for triggering in a limit violation situation. The user can set the
limit values with the
High trigger level
and
Low trigger level
parameters of the
corresponding analog channel. Both high level and low level violation triggering can be
active simultaneously for the same analog channel. If the duration of the limit violation
condition exceeds the filter time of approximately 50 ms, the recorder triggers. In case of
Section 8
1MAC059074-MB A
Measurement functions
938
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......