Table 868:
29GS Output signals
Name
Type
Description
SELECTED
BOOLEAN
Object selected
EXE_OP
BOOLEAN
Executes the command for open direction
EXE_CL
BOOLEAN
Executes the command for close direction
OPENPOS
BOOLEAN
Apparatus open position
CLOSEPOS
BOOLEAN
Apparatus closed position
OKPOS
BOOLEAN
Apparatus position is ok
OPEN_ENAD
BOOLEAN
Opening is enabled based on the input status
CLOSE_ENAD
BOOLEAN
Closing is enabled based on the input status
9.1.7
Settings
Table 869:
52 Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation mode disable / disable
Select timeout
10000...300000
ms
10000
30000
Select timeout in ms
Pulse length
10...60000
ms
1
200
Open and close pulse length
Control model
0=status-only
1=direct-with-
normal-security
4=sbo-with-
enhanced-security
4=sbo-with-
enhanced-security
Select control model
Operation timeout
10...60000
ms
1
500
Timeout for negative termination
Identification
CBXCBR1 switch
position
Control Object identification
Table 870:
52 Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation counter
0...10000
1
0
Breaker operation cycles
Adaptive pulse
0=False
1=True
1=True
Stop in right position
Event delay
0...10000
ms
1
200
Event delay of the intermediate position
Vendor
0
External equipment vendor
Serial number
0
External equipment serial number
Model
0
External equipment model
Section 9
1MAC059074-MB A
Control functions
968
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......