Table 881:
Status indication
Input
Status
Output
POSOPEN
POSCLOSE
POSITION
(Monitored data)
OKPOS
OPENPOS
CLOSEPOS
1=True
0=False
1=Open
1=True
1=True
0=False
0=False
1=True
2=Closed
1=True
0=False
1=True
1=True
1=True
3=Faulty/Bad
(11)
0=False
0=False
0=False
0=False
0=False
0=Intermediat
e (00)
0=False
0=False
0=False
9.2.5
Application
In the field of distribution and sub-transmission automation, the reliable control and status
indication of primary switching components both locally and remotely is in a significant
role. These features are needed especially in modern remote controlled substations. The
application area of 52-TOC, 29DS and 29GS functions covers remote and local status
indication of, for example, disconnectors, air-break switches and grounding switches,
which represent the lowest level of power switching devices without short-circuit
breaking capability.
9.2.6
Signals
Table 882:
52-TOC,29DS Input signals
Name
Type
Default
Description
POSOPEN
BOOLEAN
0=False
Signal for open position of apparatus from I/O
1)
POSCLOSE
BOOLEAN
0=False
Signal for close position of apparatus from I/O
1)
1) Not available for monitoring
Table 883:
29GS Input signals
Name
Type
Default
Description
POSOPEN
BOOLEAN
0=False
Signal for open position of apparatus from I/O
1)
POSCLOSE
BOOLEAN
0=False
Signal for close position of apparatus from I/O
1)
1) Not available for monitoring
1MAC059074-MB A
Section 9
Control functions
615 series ANSI
973
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......