Table 903:
Control line setting definition
Control line
setting
INIT_1
INIT_2
DEL_INIT_2
INIT_3
DEL_INIT_3
INIT_4
DEL_INIT_4
INIT_5
INIT_6
0
other
other
other
other
other
other
1
prot
other
other
other
other
other
2
other
prot
other
other
other
other
3
prot
prot
other
other
other
other
4
other
other
prot
other
other
other
5
prot
other
prot
other
other
other
...63
prot
prot
prot
prot
prot
prot
prot =
protection signal
other =
non-protection signal
When the corresponding bit or bits in both the
Control line
setting and the
INIT_X
line
are TRUE:
•
The
CLOSE_CB
output is blocked until the protection is reset
•
If the
INIT_X
line defined as the protection signal is activated during the
discrimination time, the AR function goes to lockout
•
If the
INIT_X
line defined as the protection signal stays active longer than the time
set by the
Max trip time
setting, the AR function goes to lockout (long trip)
•
The
UNSUC_RECL
output is activated after a pre-defined two minutes (alarming
ground-fault).
9.4.3.2
Zone coordination
Zone coordination is used in the zone sequence between local protection units and
downstream devices. At the falling edge of the
INC_SHOTP
line, the value of the shot
pointer is increased by one, unless a shot is in progress or the shot pointer already has the
maximum value.
The falling edge of the
INC_SHOTP
line is not accepted if any of the shots are in progress.
9.4.3.3
Master and slave scheme
With the cooperation between the AR units in the same protection relay or between
protection relays, sequential reclosings of two breakers at a line end in a 1½-breaker,
double breaker or ring-bus arrangement can be achieved. One unit is defined as a master
and it executes the reclosing first. If the reclosing is successful and no trip takes place, the
1MAC059074-MB A
Section 9
Control functions
615 series ANSI
993
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......