Table 9. Binary inputs
Description
Value
Operating range
±20% of the rated voltage
Rated voltage
24...250 V DC
Current drain
1.6...1.9 mA
Power consumption
31.0...570.0 mW
Threshold voltage
16...176 V DC
Reaction time
<3 ms
Table 10. RTD/mA measurement (XRGGIO130)
Description
Value
RTD inputs
Supported RTD sensors
100 Ω platinum
250 Ω platinum
100 Ω nickel
120 Ω nickel
250 Ω nickel
10 Ω copper
TCR 0.00385 (DIN 43760)
TCR 0.00385
TCR 0.00618 (DIN 43760)
TCR 0.00618
TCR 0.00618
TCR 0.00427
Supported resistance range
0...2 kΩ
Maximum lead resistance (three-
wire measurement)
25 Ω per lead
Isolation
2 kV (inputs to protective earth)
Response time
<4 s
RTD/resistance sensing current
Maximum 0.33 mA rms
Operation accuracy
Resistance
Temperature
± 2.0% or ±1 Ω
±1°C
10 Ω copper: ±2°C
mA inputs
Supported current range
0…20 mA
Current input impedance
44 Ω ± 0.1%
Operation accuracy
±0.5% or ±0.01 mA
Table 11. Signal output X100: SO1
Description
Value
Rated voltage
250 V AC/DC
Continuous contact carry
5 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit time constant L/R<40 ms, at
48/110/220 V DC
1 A/0.25 A/0.15 A
Minimum contact load
100 mA at 24 V AC/DC
Voltage Protection and Control
1MRS757058 K
REU615
Product version: 5.0 FP1
ABB
21
Summary of Contents for Relion 615 series
Page 1: ...RELION 615 SERIES Voltage Protection and Control REU615 Product Guide...
Page 54: ...54...
Page 55: ......