Set the parameters for SSCBR1 properly.
SSCBR1
BLOCK
POSOPEN
POSCLOSE
OPEN_CB_EXE
CLOSE_CB_EXE
PRES_ALM_IN
PRES_LO_IN
SPR_CHR_ST
SPR_CHR
RST_IPOW
RST_CB_WEAR
RST_TRV_T
RST_SPR_T
TRV_T_OP_ALM
TRV_T_CL_ALM
SPR_CHR_ALM
OPR_ALM
OPR_LO
IPOW_ALM
IPOW_LO
CB_LIFE_ALM
MON_ALM
PRES_ALM
PRES_LO
OPENPOS
INVALIDPOS
CLOSEPOS
CB_OPEN_COMMAND
X110_BI8_CB_OPENED
X110_BI7_CB_CLOSED
SSCBR1_TRV_T_OP_ALM
SSCBR1_TRV_T_CL_ALM
SSCBR1_IPOW_ALM
SSCBR1_IPOW_LO
SSCBR1_MON_ALM
SSCBR1_SPR_CHR_ALM
SSCBR1_OPR_ALM
SSCBR1_OPR_LO
SSCBR1_CB_LIFE_ALM
SSCBR1_PRES_ALM
SSCBR1_PRES_LO
GUID-405FC9FC-362E-4BDD-B9FE-5F33183F06C0 V2 EN
Figure 160:
Circuit breaker condition monitoring function
OR6
B1
B2
B3
B4
B5
B6
O
OR6
B1
B2
B3
B4
B5
B6
O
OR
B1
B2
O
SSCBR1_TRV_T_OP_ALM
SSCBR1_TRV_T_CL_ALM
SSCBR1_IPOW_ALM
SSCBR1_IPOW_LO
SSCBR1_MON_ALM
SSCBR1_SPR_CHR_ALM
SSCBR1_OPR_ALM
SSCBR1_OPR_LO
SSCBR1_CB_LIFE_ALM
SSCBR1_PRES_ALM
SSCBR1_PRES_LO
SSCBR1_ALARMS
GUID-5F45857B-F5B3-4548-8BC7-AA643E7FF832 V2 EN
Figure 161:
Logic for circuit breaker monitoring alarm
Two separate trip circuit supervision functions are included: TCSSCBR1 for power
output X100:PO3 and TCSSCBR2 for power output X100:PO4. TCSSCBR1 function
is blocked by the master trip TRPPTRC1 and TRPPTRC2 and the generator circuit
breaker open signal, whereas TCSSCBR2 function is blocked by the master trip
TRPPTRC6 and the field excitation open signal.
It is assumed that there is no external resistor in the circuit-breaker
tripping coil circuit connected in parallel with the circuit breaker's
normally open auxiliary contact.
Set the parameters for TCSSCBR1 properly.
1MRS758272 B
Section 3
REG615 standard configurations
REG615
119
Application Manual