2.4.2.7
LD0.SCA4GAPC4 Analog value scaling (4) – SCA4-4
Table 176:
LD0.SCA4GAPC4 Analog value scaling (4) – SCA4-4
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.SCA4GAPC4
i16
1000
.AnValOut1.mag
AO1_VALUE
Analog value 1 after scaling
0…N
i16
1000
.AnValOut2.mag
AO2_VALUE
Analog value 2 after scaling
0…N
i16
1000
.AnValOut3.mag
AO3_VALUE
Analog value 3 after scaling
0…N
i16
1000
.AnValOut4.mag
AO4_VALUE
Analog value 4 after scaling
0…N
2.4.2.8
LD0.SPEMMTR1 Single-phase power and energy measurement (1)
Table 177:
LD0.SPEMMTR1 Single-phase power and energy measurement (1)
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.SPE1MMTR1
u32
1
.SupWh.actVal
Accumulated Reverse active
energy (high) , phase A
0...1E10
[kWh]
.SupWh.actVal
(low word)
u32
1
.SupVArh.actVal
Accumulated Reverse reactive
energy (high) , phase A
0...1E10
[kWh]
.SupVArh.actVal
(low word)
u32
1
.DmdWh.actVal
Accumulated Forward active
energy (high) , phase A
0...1E10
[kWh]
.DmdWh.actVal
(low word)
u32
1
.DmdVArh.actVal
Accumulated Forward reactive
energy (high) , phase A
0...1E10
[kWh]
.DmdVArh.actVal
(low word)
u32
1
. EnValRs.Oper.ctlVal
Reset of accumulated energy
reading
0...1E10
[kWh]
. EnValRs.Oper.ctlVal
(low word)
LD0.SPE2MMTR1
u32
1
.SupWh.actVal
Accumulated Reverse active
energy (high) , phase B
0...1E10
[kWh]
.SupWh.actVal
(low word)
u32
1
.SupVArh.actVal
Accumulated Reverse reactive
energy (high) , phase B
0...1E10
[kWh]
.SupVArh.actVal
(low word)
Table continues on next page
1MAC252756-MB B
Section 2
Modbus data mappings
REM615 ANSI
97
Point List Manual
Summary of Contents for Relion 615 series
Page 1: ...RELION 615 SERIES Motor Protection and Control REM615 ANSI Modbus Point List Manual...
Page 2: ......
Page 14: ...8...