2.3.1
Premapped indications
2.3.1.1
Common data 1
Table 4:
Common data 1
BitA
RegA
IEC 61850 name
SA name
Description
Values
CTRL.LLN0
2720
170.00
.Loc.stVal
-
Remote/Local state
0/1=Rem/Loc
2721
170.01
.LocKeyHMI.stVal.Station
-
Station state
1=Station
DR.RDRE1
2722
170.02
.RcdMade.stVal
-
DR recording made
1=Made
2723
170.03
.mcd
2.3.1.2
CTRL.CBCILO1 Circuit breaker enable signals (1)
Table 5:
CTRL.CBCILO1 Circuit breaker enable signals (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
CTRL.CBCILO1
2824
176.08
.EnaOpn.stVal
ENA_OPEN
Open enabled
1=Enabled
2825
176.09
.EnaCls.stVal
ENA_CLOSE
Close enabled
1=Enabled
2.3.1.3
CTRL.CBCSWI1 Circuit breaker (1) mom. position
Table 6:
CTRL.CBCSWI1 Circuit breaker (1) mom. position
BitA
RegA
IEC 61850 name
SA name
Description
Values
CTRL.CBCSWI1
POSITION
2804
175.04
.Pos.stVal.Close
-
Close bit
1=Close
2805
175.05
.Pos.stVal.Open
-
Open bit
1=Open
2806
175.06
.Pos.stVal.Fault
-
Fault bit
1=Pos(00/11)
2834
177.02
.SynItlByps.stVal
ITL_BYPASS
Interlock bypass
1=Bypass
2835
177.03
.mcd
1MAC252756-MB B
Section 2
Modbus data mappings
REM615 ANSI
21
Point List Manual