2.3.1.7
CTRL.DCSXSWI2 Disconnector position indication (2) – 29DS-1
Table 10:
CTRL.DCSXSWI2 Disconnector position indication (2) – 29DS-1
BitA
RegA
IEC 61850 name
SA name
Description
Values
CTRL.DCSXSWI2
POSITION
2795
174.11
.Pos.stVal.Close
-
Close bit
1=Close
2796
174.12
.Pos.stVal.Open
-
Open bit
1=Open
2797
174.13
.Pos.stVal.Fault
-
Fault bit
1=Pos(00/11)
2.3.1.8
CTRL.DCSXSWI3 Disconnector position indication (3) – 29DS-2
Table 11:
CTRL.DCSXSWI3 Disconnector position indication (3) – 29DS-2
BitA
RegA
IEC 61850 name
SA name
Description
Values
CTRL.DCSXSWI3
POSITION
2798
174.14
.Pos.stVal.Close
-
Close bit
1=Close
2799
174.15
.Pos.stVal.Open
-
Open bit
1=Open
2800
175.00
.Pos.stVal.Fault
-
Fault bit
1=Pos(00/11)
2.3.1.9
CTRL.DCXSWI1 Disconnector control (1) – 29DS-1
Table 12:
CTRL.DCXSWI1 Disconnector control (1) – 29DS-1
BitA
RegA
IEC 61850 name
SA name
Description
Values
CTRL.DCXSWI1
POSITION
3472
217.00
.Pos.stVal.Close
-
Close bit
1=Close
3473
217.01
.Pos.stVal.Open
-
Open bit
1=Open
3474
217.02
.Pos.stVal.Fault
-
Fault bit
1=Pos(00/11)
3475
217.03
.Pos.stSeld
-
Control selected
1=Selected
CTRL.DCCILO1
3476
217.04
.EnaOpn.stVal
ENA_OPEN
Open enabled
1=Enabled
3477
217.05
.EnaCls.stVal
ENA_CLOSE
Close enabled
1=Enabled
CTRL.DCXSWI1
3478
217.06
.BlkOpn.stVal
BLK_OPEN
Open blocked
1=Blocked
3479
217.07
.mcd
3480
217.08
.BlkCls.stVal
BLK_CLOSE
Close blocked
1=Blocked
3481
217.09
.mcd
CTRL.DCCILO1
3482
217.10
.ItlByps.stVal
ITL_BYPASS
Interlock bypass
1=Bypass
3483
217.11
.mcd