2.3.1.18
LD0.CCSPVC1 Current circuit supervision (1) – CCM-1
Table 21:
LD0.CCSPVC1 Current circuit supervision (1) – CCM-1
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.CCSPVC1
2936
183.08
.SigFailAlm.stVal
ALARM
Alarm
1=Alarm
2937
183.09
.mcd
2938
183.10
.FailACirc.general
FAIL
Failure trip
1=Trip
2939
183.11
.mcd
2.3.1.19
LD0.CMMXU1 Three-phase current measurement (1) – IA, IB, IC
Table 22:
LD0.CMMXU1 Three-phase current measurement (1) – IA, IB, IC
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.CMMXU1
2752
172.00
.HiAlm.stVal
HIGH_ALARM
High alarm
1=Alarm
2753
172.01
.mcd
2754
172.02
.HiWrn.stVal
HIGH_WARN
High warning
1=Warning
2755
172.03
.mcd
2756
172.04
.LoWrn.stVal
LOW_WARN
Low warning
1=Warning
2757
172.05
.mcd
2758
172.06
.LoAlm.stVal
LOW_ALARM
Low alarm
1=Alarm
2759
172.07
.mcd
2.3.1.20
LD0.DEFLPDEF1 Directional ground-fault protection, low stage (1) –
67/51N-1
Table 23:
LD0.DEFLPDEF1 Directional ground-fault protection, low stage (1) – 67/51N-1
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.DEFLPTOC1
2900
181.04
.Str.general
PICKUP
Stage pickup
1=Pickup
2901
181.05
.mcd
2902
181.06
.Op.general
TRIP
Stage trip
1=Trip
2903
181.07
.mcd
1MAC252756-MB B
Section 2
Modbus data mappings
REM615 ANSI
27
Point List Manual
Summary of Contents for Relion 615 series
Page 1: ...RELION 615 SERIES Motor Protection and Control REM615 ANSI Modbus Point List Manual...
Page 2: ......
Page 14: ...8...
Page 114: ...108...