2.4.1.12
Fault record structure header
Table 135:
Fault record structure header
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
Selection write
9401
i16
1
Read selection
-99…3
Record data header
9402
u16
1
Record sequence num
0...65535
9403
u16
1
Unread records left
0...99
Timestamp of record
9404
u16
1
Year, month
Year/Month
9405
u16
1
Day, hour
Day/Hour
9406
u16
1
Minute, second
Min/Sec
9407
u16
1
Millisecond
Millisecond
9408
u16
1
Timestamp quality
2.4.1.13
Fault record data
The table shows all potential data available in the fault record application. Which data is
actually recorded depends on the functions available and enabled in the protection relay's
configuration.
Table 136:
Fault record data
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.FLTRFRC1
Fault record data
9409
u32
1
.OpCnt.stVal
Fault record number (high)
0..999999
9410
(Low word)
9411
i16
1
.ProFnc.stVal
Protection function
-32768...3276
7
9412
u16
100
.Hz.mag
Frequency
30…80.00
[Hz]
9413
u16
100
.StrDur.mag
Start duration
0...100.00 [%]
9414
u32
1000
.StrOpTm.mag
Operate time [ms] (high)
0...999999.99
9
9415
(Low word)
9416
u32
100
.FltPtR.mag
Fault resistance
0.00…
1000000.00
ohms
9417
(Low word)
Table continues on next page
Section 2
1MAC252756-MB B
Modbus data mappings
76
REM615 ANSI
Point List Manual