RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
9418
u32
100
.FltDiskm.mag
Fault distance
0.00…
9999.99 pu
9419
(Low word)
9420
u16
1
.ActSetGr.stVal
Active setting group
1…6
9421
u16
1
.ShotPntr.stVal
AR shot pointer value
0...7
Captured values during fault
9422
u16
1000
.Max50DifAA.mag
Max. diff. current phs A
0.000...80.000
[pu]
9423
u16
1000
.Max50DifAB.mag
Max. diff. current phs B
0.000...80.000
[pu]
9424
u16
1000
.Max50DifAC.mag
Max. diff. current phs C
0.000...80.000
[pu]
9425
u16
1000
.Max50RstAA.mag
Max. bias current phs A
0.000…
50.000 [pu]
9426
u16
1000
.Max50RstAB.mag
Max. bias current phs B
0.000…
50.000 [pu]
9427
u16
1000
.Max50RstAC.mag
Max. bias current phs C
0.000…
50.000 [pu]
9428
u16
1000
.DifAPhsA.mag
Diff. current phs A
0.000...80.000
[pu]
9429
u16
1000
.DifAPhsB.mag
Diff. current phs B
0.000...80.000
[pu]
9430
u16
1000
.DifAPhsC.mag
Diff. current phs C
0.000...80.000
[pu]
9431
u16
1000
.RstAPhsA.mag
Bias current phs A
0.000…
50.000 [pu]
9432
u16
1000
.RstAPhsB.mag
Bias current phs B
0.000…
50.000 [pu]
9433
u16
1000
.RstAPhsC.mag
Bias current phs C
0.000…
50.000 [pu]
9434
u16
1000
.DifARes.mag
Diff. current Io
0.000...80.000
[pu]
9435
u16
1000
.RstARes.mag
Bias current Io
0.000…
50.000 [pu]
9436
u16
1000
.Max50APhsA1.mag
Max. current phs A(1)
0.000…
50.000 [×In]
9437
u16
1000
.Max50APhsB1.mag
Max. current phs B(1)
0.000…
50.000 [×In]
9438
u16
1000
.Max50APhsC1.mag
Max. current phs C(1)
0.000…
50.000 [×In]
9439
u16
1000
.Max50ARes1.mag
Max. current Io(1)
0.000…
50.000 [×In]
9440
u16
1000
.APhsA1.mag
Current phs A(1)
0.000…
50.000 [×In]
Table continues on next page