2.4.1.36
LD0.PEMMXU1 Power measurement demand values (1) – P, E-1
Table 159:
LD0.PEMMXU1 Power measurement demand values (1) – P, E-1
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.PEAVMMXU1
Demand value
1939
i32
1
.TotW.mag
Active power P (high)
-/+ 999,999
1940
(Low word)
1941
i32
1
.TotVAr.mag
Reactive power Q (high)
-/+ 999,999
1942
(Low word)
1943
i32
1
.TotVA.mag
Apparent power S (high)
-/+ 999,999
1944
(Low word)
1945
i16
1000
.TotPF.mag
Power factor
-1…1
LD0.PEMAMMXU1
Max demand value
i32
1
.TotW.mag
Active power P
-/+ 999,999
i32
1
.TotVAr.mag
Reactive power Q
-/+ 999,999
i32
1
.TotVA.mag
Apparent power S
-/+ 999,999
LD0.PEMIMMXU1
Min demand value
i32
1
.TotW.mag
Active power P
-/+ 999,999
i32
1
.TotVAr.mag
Reactive power Q
-/+ 999,999
i32
1
.TotVA.mag
Apparent power S
-/+ 999,999
2.4.1.37
LD0.PEMMXU1 Three-phase power and energy measurement (1) – P, E-1
Table 160:
LD0.PEMMXU1 Three-phase power and energy measurement (1) – P, E-1
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.PEMMXU1
161
i32
1
.TotW.instMag
P_INST
Total active power P (high)
-/+ 999,999
162
.TotW.instMag
(low word)
163
i32
1
.TotVAr.instMag
Q_INST
Total reactive power Q (high)
-/+ 999,999
164
.TotVAr.instMag
(low word)
165
i32
1
.TotVA.instMag
S_INST
Total apparent power S (high)
-/+ 999,999
166
.TotVA.instMag
(low word)
167
i16
1000
.TotPF.instMag
PF_INST
Average power factor
-1...1
Section 2
1MAC252756-MB B
Modbus data mappings
90
REM615 ANSI
Point List Manual