background image

Relion

®

 615 series

Line Differential Protection and Control

RED615

DNP3 Point List Manual

Summary of Contents for Relion 615 series

Page 1: ...Relion 615 series Line Differential Protection and Control RED615 DNP3 Point List Manual...

Page 2: ......

Page 3: ...Document ID 1MRS756879 Issued 2013 02 21 Revision D Product version 4 0 FP1 Copyright 2013 ABB All rights reserved...

Page 4: ...s document is furnished under a license and may be used copied or disclosed only in accordance with the terms of such license Trademarks ABB and Relion are registered trademarks of the ABB Group All o...

Page 5: ...roduct failure would create a risk for harm to property or persons including but not limited to personal injuries or death shall be the sole responsibility of the person or entity applying the equipme...

Page 6: ...rning electrical equipment for use within specified voltage limits Low voltage directive 2006 95 EC This conformity is the result of tests conducted by ABB in accordance with the product standards EN...

Page 7: ...protection 14 CTRL Dxxxxx1 Controllable disconnector 1 14 CTRL Dxxxxx2 Controllable disconnector 2 15 CTRL Exxxxx1 Controllable earth switch 1 15 Sensors and monitoring functions 15 LD0 SSCBR1 Circuit...

Page 8: ...th fault protection 3 20 LD0 HAEFPTOC1 Harmonics based earth fault protection 20 LD0 INPHAR1 Three phase inrush detection 20 LD0 INTRPTEF1 Transient intermittent earth fault protection 20 LD0 LNPDIF1...

Page 9: ...s 28 LD0 LLN0 LPHD1 Reset indications and LEDs reset device 28 LD0 DNPGGIO1 Parameter setting group control 28 Switchgear functions 29 CTRL CBCSWI1 Circuit breaker control 29 CTRL DCCSWI1 Controllable...

Page 10: ...ues 35 CTRL ESSXSWI1 Earth switch 1 4 pole 2 bit position values 35 CTRL ESSXSWI2 Earth switch 2 4 pole 2 bit position values 35 CTRL ESXSWI1 Controllable earth switch 1 4 pole 2 bit position values 3...

Page 11: ...be used to find out when and for what purpose a typical protection function can be used The manual can also be used when calculating settings The communication protocol manual describes a communicatio...

Page 12: ...D The manual should be used in conjunction with the corresponding communication protocol manual The technical manual contains application and functionality descriptions and lists function blocks logic...

Page 13: ...ution notices 1 4 2 Document conventions A particular convention may not be used in this manual Abbreviations and acronyms in this manual are spelled out in the glossary The glossary also contains def...

Page 14: ...EFPADM1 Yo 1 21YN 1 EFPADM2 Yo 2 21YN 2 EFPADM3 Yo 3 21YN 3 Wattmetric based earth fault protection WPWDE1 Po 1 32N 1 WPWDE2 Po 2 32N 2 WPWDE3 Po 3 32N 3 Transient intermittent earth fault protection...

Page 15: ...tion ESSXSWI1 I O ES 1 I O ES 1 ESSXSWI2 I O ES 2 I O ES 2 Auto reclosing DARREC1 O I 79 Condition monitoring Circuit breaker condition monitoring SSCBR1 CBCM CBCM Trip circuit supervision TCSSCBR1 TC...

Page 16: ...10...

Page 17: ...ignments are Class 0 and Class 1 for binary inputs and Class 0 and Class 2 for analog inputs These assignments can be modified later Analog values are provided with default scalings The scalings can b...

Page 18: ...V1 ROVPTOV2 ROVPTOV3 T1PTTR1 BSTGGIO1 LNPLDF1 CCBRBRF1 INRPHAR1 TRPPTRC1 TRPPTRC2 CBXCBR1 DCXSWI1 DCXSWI2 ESXSWI1 DCSXSWI1 DCSXSWI2 DCSXSWI3 ESSXSWI1 ESSXSWI2 DARREC1 o o SSCBR1 TCSSCBR1 TCSSCBR2 CCRD...

Page 19: ...s visible for example in ACT Description Short description of the signal See the application function block documentation for more details Value Meaning of the input states 2 3 1 System functions 2 3...

Page 20: ...Open blocked 1 Blocked CTRL CCBRBRF1 OpEx general TRBU Failure ext trip 1 Failure OpIn general TRRET Operate re trip 1 Operate Str general CB_FAULT_AL Start timer running 1 Start 2 3 2 2 CTRL Dxxxxx1...

Page 21: ...bled EnaOpn stVal ENA_OPEN Open enabled 1 Enabled ItlByPss stVal ITL_BYPASS Interlocking bypass 1 Bypassed CTRL ESCSWI1 Pos stSeld SELECTED CB selected 1 Selected CTRL ESXSWI1 BlkCls stVal BLK_CLOSE C...

Page 22: ...on 2 IEC 61850 name SA name Description Values LD0 TCSSCBR2 CirAlm stVal ALARM Supervision alarm 1 Alarm 2 3 3 4 LD0 BSTGGIO1 Binary signal transfer supervision Table 13 LD0 BSTGGIO1 Binary signal tra...

Page 23: ...ion functions 2 3 5 1 LD0 LEDPTRC1 Global protection signals Table 17 LD0 LEDPTRC1 Global protection signals IEC 61850 name SA name Description Values LD0 LEDPTRC1 Global protection signals Op general...

Page 24: ...e 1 IEC 61850 name SA name Description Values LD0 DEFLPTOC1 Low stage 1 Op general OPERATE Operate 1 Operate Str general START Start 1 Start 2 3 5 6 LD0 DEFLPDEF2 Directional earth fault protection lo...

Page 25: ...escription Values LD0 EFLPTOC1 Low stage 1 Op general OPERATE Operate 1 Operate Str general START Start 1 Start 2 3 5 10 LD0 EFLPTOC2 Non directional earth fault and sensitive earth fault protection l...

Page 26: ...ased earth fault protection Table 30 LD0 HAEFPTOC1 Harmonics based earth fault protection IEC 61850 name SA name Description Values LD0 HAEFPTOC1 Op general OPERATE Stage operate 1 Operate Str general...

Page 27: ...LD0 NSPTOC2 Negative sequence overcurrent protection 2 IEC 61850 name SA name Description Values LD0 NSPTOC2 Op general OPERATE Stage operate 1 Operate Str general START Stage start 1 Start 2 3 5 20...

Page 28: ...ction low stage 1 Table 40 LD0 PHLPTOC1 Phase overcurrent protection low stage 1 IEC 61850 name SA name Description Values LD0 PHLPTOC1 Op general OPERATE Stage operate 1 Operate Str general START Sta...

Page 29: ...5 LD0 WPWDE1 Wattmetric based earth fault protection 1 IEC 61850 name SA name Description Values LD0 WPDSE1 Str general START Stage 1 start 1 Start Op general OPERATE Stage 1 operate 1 Operate 2 3 5 3...

Page 30: ...gress 1 In progress CBManCls stVal MAN_CB_CL CB manually closed 1 CB closed LO stVal LOCKED Lockout status 1 Lockout UnsRec stVal UNSUC_RECL Reclose fail status 1 Failed InBlkThm stVal Thermal block s...

Page 31: ...scription Values LD0 MVGAPC1 Q1 stVal Input 1 signal 0 1 Off On Q2 stVal Input 2 signal 0 1 Off On Q3 stVal Input 3 signal 0 1 Off On Q4 stVal Input 4 signal 0 1 Off On Q5 stVal Input 5 signal 0 1 Off...

Page 32: ...al Output 8 state 0 1 Off On SPCS09 stVal Output 9 state 0 1 Off On SPCS10 stVal Output 10 state 0 1 Off On SPCS11 stVal Output 11 state 0 1 Off On SPCS12 stVal Output 12 state 0 1 Off On SPCS13 stVal...

Page 33: ...tVal X110 Output 4 1 0 ON OFF 2 3 8 3 LD0 XGGIO120 Physical I O Table 57 LD0 XGGIO120 Physical I O IEC 61850 name SA name Description Values LD0 XGGIO120 Ind1 stVal X120 Input 1 1 0 ON OFF Ind2 stVal...

Page 34: ...ly be controlled with value On Writing Off to these points does not affect the function of the output See DNP3 control relay output block parameters 2 4 1 System functions 2 4 1 1 LD0 LLN0 LPHD1 Reset...

Page 35: ...TRL DCCSWI2 Pos Oper ctlVal Disconnector control On Off 2 4 2 4 CTRL ESCSWI2 Controllable earth switch 2 control Table 65 CTRL ESCSWI2 Controllable earth switch 2 control IEC 61850 name SA name Descri...

Page 36: ...Pulse type outputs are triggered with the write value 1 Persistent type outputs can be written with both 1 and 0 values The persistent type is the same as the toggled mode on LHMI and WHMI Table 69 L...

Page 37: ...Output 2 control On Off SPCS03 ctlVal Output 3 control On Off SPCS04 ctlVal Output 4 control On Off SPCS05 ctlVal Output 5 control On Off SPCS06 ctlVal Output 6 control On Off SPCS07 ctlVal Output 7 c...

Page 38: ...escription IEC 61850 name Original IED data object identification Described in the IEC 61850 format as Logical Device Logical Node and thereafter Data Object Data Attribute Logical Node is the same as...

Page 39: ...cTrg stVal Num of watchdog resets 0 65535 R 0 65535 0 65535 WrmStr stVal Num of warm starts 0 65535 R 0 65535 0 65535 2 5 1 3 LD0 DNPGGIO1 Active parameter setting group Table 76 LD0 DNPGGIO1 Active p...

Page 40: ...position value IEC 61850 name SA name Description Values S Arg 1 2 3 4 CTRL CBCSWI1 Pos stVal POSITION Intermediate 0 Off 1 On 2 Bad 3 0 3 R 0 3 0 3 2 5 2 2 CTRL DCSXSWI1 Disconnector 1 4 pole 2 bit p...

Page 41: ...n values Table 83 CTRL DCXSWI2 Controllable disconnector 2 4 pole 2 bit position values IEC 61850 name SA name Description Values S Arg 1 2 3 4 CTRL DCXSWI2 Pos stVal POSITION Intermediate 0 Off 1 On...

Page 42: ...magnitude 0 00 40 0 xIn R 0 40 0 4000 A phsC instCVal mag I_INST_C phsC magnitude 0 00 40 0 xIn R 0 40 0 4000 2 5 3 2 LD0 RESCMMXU1 Residual current 1 Table 88 LD0 RESCMMXU1 Residual current 1 IEC 618...

Page 43: ...4 1 LD0 T1PTTR1 Temperature protection values 1 Table 92 LD0 T1PTTR1 Temperature protection values 1 IEC 61850 name SA name Description Values S Arg 1 2 3 4 LD0 T1PTTR1 Tmp mag Object temperature 100...

Page 44: ...rbance recorder values IEC 61850 name SA name Description Values S Arg 1 2 3 4 DR RDRE1 FltNum stVal Number of recordings 0 65535 R 0 65535 0 65535 MemUsed stVal Rec memory used 0 100 R 0 100 0 100 Se...

Page 45: ...supported the complete list is described in the attached table For static non change event object requests request qualifier codes 07 and 08 limited quantity and 17 and 28 index are supported Static...

Page 46: ...ount 1 Count 1 is accepted but ignored Never Always Sometimes Configurable Pulse on Never Always Sometimes Configurable Pulse off Never Always Sometimes Configurable Latch on Never Always Sometimes Co...

Page 47: ...rt Append file mode Yes No Custom status code strings Yes No Permissions field Yes No File events assigned to class Yes No File events send immediately Yes No Multiple blocks in a fragment Yes No Max...

Page 48: ...unsol resp 17 28 index 2 21 Binary input change with time 1 read 06 no range or all 07 08 limited qty 129 response 130 unsol resp 17 28 index 2 3 Binary input change with relative time 1 read 06 no r...

Page 49: ...p 17 28 index 32 2 16 bit analog change event without time 1 read 06 no range or all 07 08 limited qty 129 response 130 unsol resp 17 28 index 32 3 32 bit analog change event with time 1 read 06 no ra...

Page 50: ...estart 4 No object function code only 23 delay meas No object function code only 24 record current time 1 A default variation refers to the variation responded when variation 0 is requested and or in...

Page 51: ...has the ownership of the protocol and assumes responsibility for its evolution EMC Electromagnetic compatibility HMI Human machine interface IEC International Electrotechnical Commission IEC 61850 Int...

Page 52: ...46...

Page 53: ...47...

Page 54: ......

Page 55: ......

Page 56: ...P O Box 699 FI 65101 VAASA Finland Phone 358 10 22 11 Fax 358 10 22 41094 ABB Limited Distribution Automation Maneja Vadodara 390013 India Phone 91 265 2604032 Fax 91 265 2638922 www abb com substati...

Reviews: