curve type "Inverse reset", the reset time depends on the current during the drop-off
situation. If the drop-off situation continues, the reset timer is reset and the
PICKUP
output is deactivated.
The "Inverse reset" selection is only supported with ANSI or the
programmable types of the IDMT operating curves. If another operating
curve type is selected, an immediate reset occurs during the drop-off
situation.
The setting
Time multiplier
is used for scaling the IDMT operation and reset times.
The setting parameter
Minimum trip time
defines the minimum desired operation time for
IDMT. The setting is applicable only when the IDMT curves are used
The
Minimum trip time
setting should be used with great care because the
operation time is according to the IDMT curve but always at least the
value of the
Minimum trip time
setting. More information can be found in
IDMT curves for overcurrent protection
.
Timer calculates the pickup duration value PICKUP_DUR, which indicates the
percentage ratio of the pickup situation, and the set operating time, which can be either
according to DT or IDMT. The value is available in the monitored data view.
More information can be found in the
General function block features
.
Blocking logic
There are three operation modes in the blocking function. The operation modes are
controlled by the
BLOCK
input and the global setting in
Configuration/System/Blocking
mode
which selects the blocking mode. The
BLOCK
input can be controlled by a binary
input, a horizontal communication input or an internal signal of the protection relay's
program. The influence of the
BLOCK
signal activation is preselected with the global
setting
Blocking mode
.
The
Blocking mode
setting has three blocking methods. In the "Freeze timers" mode, the
operation timer is frozen to the prevailing value, but the
TRIP
output is not deactivated
when blocking is activated. In the "Block all" mode, the whole function is blocked and the
timers are reset. In the "Block TRIP output" mode, the function operates normally but the
TRIP
output is not activated.
4.2.5.5
Application
During a ground fault, 51NHA calculates the maximum current for the current feeder. The
value is sent over an analog GOOSE to other protection relays of the busbar in the
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
405
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......