Characteristic
Value
Trip time accuracy in IDMT mode
3)
±5.0% of the set value or ±20 ms
Suppression of harmonics
-50 dB at f = f
n
-3 dB at f = 13 × f
n
1) Fundamental frequency current = 1.0 × I
n
, harmonics current before fault = 0.0 × I
n
, harmonics fault current
2.0 ×
Pickup value, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum
Pickup value = 2.5 × I
n
,
Pickup value multiples in range of 2...20
4.2.5.10
Technical revision history
Table 397:
51NHA Technical revision history
Technical revision
Change
B
Internal improvement.
C
Internal improvement.
4.2.6
Wattmetric-based ground-fault protection 32N
4.2.6.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Wattmetric-based ground-fault
protection
WPWDE
Po> ->
32N
4.2.6.2
Function block
TRIP
PICKUP
IG
32N
VG
BLOCK
RCA_CTL
GUID-4C60F4EA-02BE-4E2A-AEE4-CFC5B15A4B08 V1 EN
Figure 196:
Function block
4.2.6.3
Functionality
The wattmetric-based ground-fault protection function 32N can be used to detect ground
faults in ungrounded networks, compensated networks (Petersen coil-grounded
networks) or networks with a high-impedance grounding. It can be used as an alternative
solution to the traditional residual current-based ground-fault protection functions, for
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
409
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......